Heat, Ventilation and Air-Conditioning
• |
Six (6) 985TR fresh water cooled chillers at 2/F |
• |
Centralized chilled water system with VAV air handling unit and VAV terminal units for the office towers |
• |
Approximately 110TR per office floor |
• |
Two (2) 300TR 24-hour air-cooled chiller backed up by standby generator at the roof for the two office towers to provide 16TR essential cooling for each office floor |
• |
Electric duct heaters to VAV terminal units serving perimeter zone of office |
• |
Design based on 9m2/person for typical office areas |
• |
Fresh air provision : 10 l/s/person |
Electrical Supply
• |
19nos. of 1500KVA transformers |
• |
Two groups of HV cables feed to building |
• |
Approximately 110TR per office floor |
• |
Two (2) 300TR 24-hour air-cooled chiller backed up by standby generator at the roof for the two office towers to provide 16TR essential cooling for each office floor |
• |
Dual power supply risers for each office floor |
• |
250A TPN for each office floor |
Data Communication Network
• |
Vertical and horizontal trunkings in the meter rooms of each office floor for office tenants to install communication networks between floors |
• |
Communal Aerial Broadcast Distribution (CABD) |
• |
TV/FM antenna and one dish antenna installed on the roof |
Satellite Master Antenna
• |
Space on roof for additional satellite dish |
Television (SMATV) System
Security System
• |
24-hour monitoring inclusive of CCTV, Microprocessor based carpark control, watchman tour and panic alarm |
Gas
|